Example D1(a), one-family dwelling, standard method (2023) · NEC 2023NFPA 70 (National Electrical Code), Informative Annex D, Example D1(a), 2023 editionInputs- Floor area (outside dimensions, habitable): 1,500 ft²
- Small-appliance circuits: 2
- Laundry circuits: 1
- Range or cooking (total): 12 kW
- Clothes dryer: 5.5 kW
- Water heater: 0 kW
- Dishwasher: 0 kW
- Disposal: 0 kW
- Other fixed appliances (total): 0 kW
- A/C or heat-pump compressor: 0 kVA
- Electric heat: None
- EV charger (nameplate): 0 kW
- Service voltage: 120/240 V
- Method: Standard (Part III)
| 18,600 VA · 78 A | 18,600 VA · 78 A | ✓ pass |
Example D1(a), one-family dwelling, standard method (2026) · NEC 2026NFPA 70 (National Electrical Code), Informative Annex D, Example D1(a), 2026 edition (balloted revision)Inputs- Floor area (outside dimensions, habitable): 1,500 ft²
- Small-appliance circuits: 2
- Laundry circuits: 1
- Range or cooking (total): 12 kW
- Clothes dryer: 5.5 kW
- Water heater: 0 kW
- Dishwasher: 0 kW
- Disposal: 0 kW
- Other fixed appliances (total): 0 kW
- A/C or heat-pump compressor: 0 kVA
- Electric heat: None
- EV charger (nameplate): 0 kW
- Service voltage: 120/240 V
- Method: Standard (Part III)
| 18,075 VA · 75 A | 18,075 VA · 75 A | ✓ pass |
Example D2(a), optional method, heating larger than A/C (2023) · NEC 2023NFPA 70 (National Electrical Code), Informative Annex D, Example D2(a), 2023 editionInputs- Floor area (outside dimensions, habitable): 1,500 ft²
- Small-appliance circuits: 2
- Laundry circuits: 1
- Range or cooking (total): 12 kW
- Clothes dryer: 5 kW
- Water heater: 2.5 kW
- Dishwasher: 1.2 kW
- Disposal: 0 kW
- Other fixed appliances (total): 0 kW
- A/C or heat-pump compressor: 1.38 kVA
- Electric heat: Space heat, 4+ units
- Electric heat: 9 kW
- EV charger (nameplate): 0 kW
- Service voltage: 120/240 V
- Method: Optional (one dwelling)
| 21,480 VA · 90 A | 21,480 VA · 90 A | ✓ pass |
Example D2(a), optional method, heating larger than A/C (2026) · NEC 2026NFPA 70 (National Electrical Code), Informative Annex D, Example D2(a), 2026 edition (balloted revision)Inputs- Floor area (outside dimensions, habitable): 1,500 ft²
- Small-appliance circuits: 2
- Laundry circuits: 1
- Range or cooking (total): 12 kW
- Clothes dryer: 5 kW
- Water heater: 2.5 kW
- Dishwasher: 1.2 kW
- Disposal: 0 kW
- Other fixed appliances (total): 0 kW
- A/C or heat-pump compressor: 1.38 kVA
- Electric heat: Space heat, 4+ units
- Electric heat: 9 kW
- EV charger (nameplate): 0 kW
- Service voltage: 120/240 V
- Method: Optional (one dwelling)
| 19,680 VA · 82 A | 19,680 VA · 82 A | ✓ pass |
Example D2(b), optional method, A/C larger than heating (2023) · NEC 2023NFPA 70 (National Electrical Code), Informative Annex D, Example D2(b), 2023 editionInputs- Floor area (outside dimensions, habitable): 1,500 ft²
- Small-appliance circuits: 2
- Laundry circuits: 1
- Range or cooking (total): 13.1 kW
- Clothes dryer: 5 kW
- Water heater: 4.5 kW
- Dishwasher: 1.2 kW
- Disposal: 0 kW
- Other fixed appliances (total): 0 kW
- A/C or heat-pump compressor: 10.08 kVA
- Electric heat: Space heat, 1–3 units
- Electric heat: 1.5 kW
- EV charger (nameplate): 0 kW
- Service voltage: 120/240 V
- Method: Optional (one dwelling)
| 29,200 VA · 122 A | 29,200 VA · 122 A | ✓ pass |
Example D2(b), optional method, A/C larger than heating (2026) · NEC 2026NFPA 70 (National Electrical Code), Informative Annex D, Example D2(b), 2026 edition (balloted revision)Inputs- Floor area (outside dimensions, habitable): 1,500 ft²
- Small-appliance circuits: 2
- Laundry circuits: 1
- Range or cooking (total): 13.1 kW
- Clothes dryer: 5 kW
- Water heater: 4.5 kW
- Dishwasher: 1.2 kW
- Disposal: 0 kW
- Other fixed appliances (total): 0 kW
- A/C or heat-pump compressor: 10.08 kVA
- Electric heat: Space heat, 1–3 units
- Electric heat: 1.5 kW
- EV charger (nameplate): 0 kW
- Service voltage: 120/240 V
- Method: Optional (one dwelling)
| 27,400 VA · 114 A | 27,400 VA · 114 A | ✓ pass |
Example D2(c), optional method, heat pump with supplemental heat (2023) · NEC 2023NFPA 70 (National Electrical Code), Informative Annex D, Example D2(c), 2023 editionInputs- Floor area (outside dimensions, habitable): 2,000 ft²
- Small-appliance circuits: 2
- Laundry circuits: 1
- Range or cooking (total): 12 kW
- Clothes dryer: 5 kW
- Water heater: 4.5 kW
- Dishwasher: 1.2 kW
- Disposal: 0 kW
- Other fixed appliances (total): 0 kW
- A/C or heat-pump compressor: 5.76 kVA
- Electric heat: Heat-pump supplemental
- Electric heat: 15 kW
- EV charger (nameplate): 0 kW
- Service voltage: 120/240 V
- Method: Optional (one dwelling)
| 34,790 VA · 145 A | 34,790 VA · 145 A | ✓ pass |
Example D2(c), optional method, heat pump with supplemental heat (2026) · NEC 2026NFPA 70 (National Electrical Code), Informative Annex D, Example D2(c), 2026 edition (balloted revision)Inputs- Floor area (outside dimensions, habitable): 2,000 ft²
- Small-appliance circuits: 2
- Laundry circuits: 1
- Range or cooking (total): 12 kW
- Clothes dryer: 5 kW
- Water heater: 4.5 kW
- Dishwasher: 1.2 kW
- Disposal: 0 kW
- Other fixed appliances (total): 0 kW
- A/C or heat-pump compressor: 5.76 kVA
- Electric heat: Heat-pump supplemental
- Electric heat: 15 kW
- EV charger (nameplate): 0 kW
- Service voltage: 120/240 V
- Method: Optional (one dwelling)
| 32,790 VA · 137 A | 32,790 VA · 137 A | ✓ pass |