Wire size calculator (NEC)
The conductor, breaker and equipment ground for a load, with the 125 % rule, derating, terminal temperatures and voltage drop worked out step by step for each NEC edition.
Calculated with electrician.wiki · https://electrician.wiki/calculators/wire-size/
New to this? AWG wire size and ampacity chart
Report a problem with this result
How to use the wire size calculator
Choose the NEC edition your inspector enforces, then the kind of circuit: a branch circuit, a feeder, or a dwelling service or main feeder sized by the 83 % rule. Enter the load in amperes, splitting it into the continuous part (anything expected to run for three hours or more, such as an EV charger, water heater, heat or store lighting) and the noncontinuous part. Pick copper or aluminum and the wire type printed on the jacket, which fixes its temperature rating, and the temperature rating of the terminals at both ends.
Then describe where the wire runs: the hottest ambient it will see, how many current-carrying conductors share the raceway or cable, whether it crosses a sunny roof, and whether you need parallel sets. Leave the voltage-drop check on to have the calculator upsize the conductors when the run is long. The answer is the conductor, the breaker or fuse, and the equipment grounding conductor, with every check written out underneath.
The sizing sequence
Every result follows the same order, and the steps are numbered the same way in the worked solution.
- Minimum ampacity at the terminals. 125 % of the continuous load plus 100 % of the noncontinuous load.
- Overcurrent device. The next standard rating at or above that figure, from the edition’s list of standard ratings. 10 A joined the list in 2023.
- Terminal temperature. 60 °C or 75 °C, from the equipment listing or from the default rule of 110.14(C)(1).
- Conditions of use. The ambient correction factor and the adjustment for more than three current-carrying conductors, applied at the wire’s own temperature rating.
- Smallest conductor that passes three checks: enough ampacity at the terminal column for step 1, enough corrected ampacity for the actual load, and protection by the breaker under 240.4.
- Voltage drop. Upsize until the drop meets your target, 3 % by default.
- Equipment grounding conductor. From Table 250.122 for the breaker, increased in proportion when step 6 made the phase conductors larger.
Continuous loads and the two ampacity checks
The 125 % rule is about heat at the terminations. A breaker and its lugs are tested at 80 % of their rating for continuous duty, so the conductor attached to them is sized for 125 % of a continuous load:
That check uses the ampacity in the terminal’s temperature column, before any correction. A separate check applies the correction and adjustment factors to the conductor’s own rating and compares the result with the actual load, without the 125 %. Doing both at once, multiplying the load by 1.25 and then dividing by the derating factors, double-counts and makes the wire bigger than the Code requires. For the default 48 A charger the first check needs 60 A at 75 °C and the second 48 A after correction; 6 AWG copper passes both with 65 A.
| Rule | NEC 2017 | NEC 2020 | NEC 2023 | NEC 2026 |
|---|---|---|---|---|
| Branch circuit: 125 % of continuous load | 210.19(A)(1) | 210.19(A)(1) | 210.19(A)(1) | 210.19(A)(1) |
| Feeder: 125 % of continuous load | 215.2(A)(1) | 215.2(A)(1) | 215.2(A)(1) | 215.4(A)(1) |
| Feeder overcurrent device | 215.3 | 215.3 | 215.3 | 215.5 |
| Ampacity table | Table 310.15(B)(16) | Table 310.16 | Table 310.16 | Table 310.16 |
| Ambient correction | Table 310.15(B)(2)(a) | Table 310.15(B)(1) | Table 310.15(B)(1)(1) | Table 310.15(B)(1)(1) |
| More than three conductors | Table 310.15(B)(3)(a) | Table 310.15(C)(1) | Table 310.15(C)(1) | Table 310.15(C)(1) |
| Dwelling services (83 %) | 310.15(B)(7) | 310.12 | 310.12 | 310.12 |
| EGC increased with the phase conductors | 250.122(B) | 250.122(B) | 250.122(B) | 250.122(D) |
Why the terminal rating changes the answer
A 90 °C conductor only runs at 90 °C if both ends can take the heat. Under 110.14(C)(1), equipment for circuits of 100 A or less, or with lugs for 14 to 1 AWG, is treated as 60 °C unless it is listed and marked for 75 °C; above 100 A the default is 75 °C. Most breakers and panelboards sold today are marked 60/75 °C, which is why the calculator starts at 75 °C, but a single 60 °C device in the circuit pulls the whole circuit down. The default charger circuit needs 6 AWG copper with 75 °C terminals and 4 AWG with 60 °C terminals.
| Breaker | Copper, 60 °C terminals | Copper, 75 °C terminals | Aluminum, 60 °C | Aluminum, 75 °C |
|---|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG | 10 AWG |
| 25 A | 10 AWG | 10 AWG | 10 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 6 AWG | 8 AWG |
| 50 A | 6 AWG | 8 AWG | 4 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 3 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 2 AWG | 3 AWG |
| 80 A | 3 AWG | 4 AWG | 1 AWG | 2 AWG |
| 90 A | 2 AWG | 3 AWG | 1/0 AWG | 2 AWG |
| 100 A | 1 AWG | 3 AWG | 1/0 AWG | 1 AWG |
The 90 °C rating still earns its keep: it is the starting point for correction and adjustment. A hot attic or a full conduit derates a 90 °C conductor from a higher number, and the result often stays above the 75 °C limit.
Hot locations and full raceways
Ambient correction and the adjustment for bundled conductors both multiply the table ampacity, and they compound. Nine current-carrying 90 °C conductors at 104 °F keep 0.91 × 0.70 = 0.637 of their rating: a 40 A noncontinuous load then needs 6 AWG copper (47.78 A), where 8 AWG would manage only 35.04 A. The table shows one load across a range of conditions:
| Ambient | 3 conductors | 6 conductors | 9 conductors | 12 conductors |
|---|---|---|---|---|
| 86 °F | 8 AWG (50 A) | 8 AWG (44 A) | 8 AWG (38.5 A) | 6 AWG (37.5 A) |
| 104 °F | 8 AWG (50 A) | 8 AWG (40.04 A) | 8 AWG (35.04 A) | 4 AWG (43.23 A) |
| 122 °F | 8 AWG (45.1 A) | 8 AWG (36.08 A) | 6 AWG (43.05 A) | 4 AWG (38.95 A) |
On a roof, raceways and cables in direct sunlight within 0.75 in. of the surface (7/8 in. before 2023) add 33 °C (60 °F) to the outdoor temperature before you look up the factor (310.15(B)(2)); XHHW-2 is exempt. Raising the run on supports is usually cheaper than the larger conductor.
Upsizing for voltage drop, and the grounding conductor that follows
The NEC recommends keeping a branch circuit or feeder within 3 % voltage drop, and 5 % for both together. When the run is long, the calculator walks up the sizes until the drop fits. Making the phase conductors bigger has a consequence people miss: the wire-type equipment grounding conductor must grow in proportion to the increase in circular mils (250.122(B); 250.122(D) in 2026). Upsizing done only for ambient correction or adjustment does not count from 2020 on.
Take the 48 A charger 175 ft from the panel. 6 AWG copper drops 3.44 %, so the calculator moves to 4 AWG at 2.16 %. The 60 A breaker calls for a 10 AWG EGC, scaled by 41,740 ÷ 26,240: 16,511 cmil. 8 AWG is 16,510 cmil, just 1.48 cmil short. The rule sets a minimum area, so the strict answer is 6 AWG, and the calculator gives it with a warning that explains the edge rather than hiding it. Some inspectors accept the smaller size for a shortfall this small; ask before you rely on that.
Worked examples
A 48 A EV charger, 100 ft from the panel
1. Minimum ampacity at the terminals: 125 % of the continuous load plus the noncontinuous load (210.19(A)(1))
2. Overcurrent device: the next standard rating at or above 60 A (210.20(A), Table 240.6(A))
3. Terminal temperature (110.14(C)(1))
75 °C terminations
4. Correction and adjustment: 86 °F, 3 current-carrying conductors (Table 310.15(B)(1)(1), Table 310.15(C)(1))
5. Smallest conductor that passes: 6 AWG Cu
75 °C column 65 A ≥ 60 A ✓ · 90 °C: 75 A, held to 65 A by the 75 °C terminals ≥ 48 A ✓ · protects up to 70 A (next size up) ≥ 60 A ✓
6. Voltage drop with 6 AWG at 48 A over 100 ft (K-factor)
7. Percent of the supply voltage
8. Equipment grounding conductor for a 60 A device (Table 250.122)
For 48 A continuous on a branch circuit under NEC 2023, use 6 AWG copper on a 60 A breaker or fuse with a 10 AWG copper equipment grounding conductor; it drops 1.97 % over 100 ft.
The same charger at 175 ft: voltage drop and the borderline EGC
1. Minimum ampacity at the terminals: 125 % of the continuous load plus the noncontinuous load (210.19(A)(1))
2. Overcurrent device: the next standard rating at or above 60 A (210.20(A), Table 240.6(A))
3. Terminal temperature (110.14(C)(1))
75 °C terminations
4. Correction and adjustment: 86 °F, 3 current-carrying conductors (Table 310.15(B)(1)(1), Table 310.15(C)(1))
5. Smallest conductor that passes: 6 AWG Cu
75 °C column 65 A ≥ 60 A ✓ · 90 °C: 75 A, held to 65 A by the 75 °C terminals ≥ 48 A ✓ · protects up to 70 A (next size up) ≥ 60 A ✓
6. Voltage drop with 6 AWG at 48 A over 175 ft (K-factor)
7. Percent of the supply voltage
8. Upsize for voltage drop: 4 AWG is the smallest size within 3 %
9. Equipment grounding conductor for a 60 A device (Table 250.122)
10. The phase conductors went up from 6 AWG to 4 AWG, so the EGC goes up in proportion (250.122(B))
For 48 A continuous on a branch circuit under NEC 2023, use 4 AWG copper on a 60 A breaker or fuse with a 6 AWG copper equipment grounding conductor; it drops 2.16 % over 175 ft, up from 6 AWG (3.44 %).
A 480 V feeder in two parallel sets
1. Minimum ampacity at the terminals: 125 % of the continuous load plus the noncontinuous load (215.2(A)(1))
2. Overcurrent device: the next standard rating at or above 600 A (215.3, Table 240.6(A))
3. Terminal temperature (110.14(C)(1))
75 °C terminations
4. Correction and adjustment: 86 °F, 3 current-carrying conductors (Table 310.15(B)(1)(1), Table 310.15(C)(1))
5. Smallest conductor that passes: 2 × 350 kcmil Cu
75 °C column 310 A × 2 sets ≥ 600 A ✓ · 90 °C: 350 A, held to 310 A by the 75 °C terminals × 2 sets ≥ 500 A ✓ · protects up to 700 A (next size up) ≥ 600 A ✓
6. Effective impedance at PF 0.85 (Chapter 9, Table 9, steel conduit, copper)
7. Voltage drop with 350 kcmil at 500 A over 250 ft (Chapter 9 Table 9)
8. Percent of the supply voltage
9. Equipment grounding conductor for a 600 A device (Table 250.122)
For 400 A continuous plus 100 A noncontinuous on a feeder under NEC 2023, use 2 sets of 350 kcmil copper per phase on a 600 A breaker or fuse with a 1 AWG copper equipment grounding conductor in each raceway; it drops 1.34 % over 250 ft.
NEC Annex D, Example D7 (2026): a 175 A dwelling service at 49 °C
1. Required ampacity: 83 % of the service or feeder rating (310.12)
2. Terminal temperature (110.14(C)(1))
75 °C terminations
3. Correction and adjustment: 49 °C, 3 current-carrying conductors (Table 310.15(B)(1)(1), Table 310.15(C)(1))
4. Smallest conductor that passes: 2/0 AWG Cu
90 °C: 195 A × 0.82 × 1.00 = 159.9 A ≥ 145.25 A ✓
5. Equipment grounding conductor for a 175 A device (Table 250.122)
For a 175 A dwelling service or feeder (83 % = 145.25 A) under NEC 2026, use 2/0 AWG copper. Run as a feeder, it needs a 6 AWG copper equipment grounding conductor.
Dwelling services and the 83 % rule
A service or main feeder that carries the whole load of a one-family dwelling, or of one dwelling unit, may use conductors with an ampacity of only 83 % of its rating (310.12; 310.15(B)(7) in 2017). Household loads never all run at once, which is why the rule exists. The Code’s own worked example, Annex D Example D7, sizes a 175 A service: 83 % is 145.25 A, met by 1/0 AWG copper or 3/0 AWG aluminum at 75 °C. The 2026 edition adds a hot location, 49 °C (120 °F), where XHHW-2 keeps 0.82 of its 90 °C rating: 2/0 AWG copper (159.9 A) and 4/0 AWG aluminum (168.1 A). The calculator reproduces both.
| Rating | 83 % | Copper, 86 °F | Copper, 104 °F | Aluminum, 86 °F | Aluminum, 104 °F |
|---|---|---|---|---|---|
| 100 A | 83 A | 4 AWG | 4 AWG | 2 AWG | 2 AWG |
| 150 A | 124.5 A | 1 AWG | 1 AWG | 2/0 AWG | 2/0 AWG |
| 200 A | 166 A | 2/0 AWG | 2/0 AWG | 4/0 AWG | 4/0 AWG |
A 104 °F location changes nothing here: XHHW-2 is derated from its 90 °C value, and the result still sits above the 75 °C limit that the terminals impose. With a 75 °C conductor type the same location would push each size up.
Before 2026 the same example used 38 °C and a factor of 0.91 and reached 2/0 copper by dividing 145.25 A by 0.91 and reading the result in the 75 °C column. Applying the factor to the XHHW-2 conductor’s own 90 °C rating and capping the result at the 75 °C value, as 110.14(C) and the 2026 example do, gives 1/0 AWG at 38 °C. The 2026 edition also limits the Table 310.12(A) shortcut to conductors rated 75 °C or higher; the calculation itself is unchanged.
Common mistakes
- Reading the 90 °C column for a breaker connection. 10 AWG THHN is 40 A in the table, but 35 A on 75 °C terminals and 30 A at most by 240.4(D).
- Applying 125 % and the derating together. They are separate checks against different ampacities.
- Counting the equipment ground as current-carrying. It never is. Nor is a neutral that carries only its own circuit’s unbalanced current; the neutral of a two-phase-and-neutral circuit from a wye system, or of a wye circuit feeding mostly nonlinear loads, does count.
- Forgetting the EGC after upsizing. A bigger phase conductor for voltage drop means a bigger EGC under 250.122(B).
- Using the 83 % rule on a subpanel. It applies only to the service or a feeder that carries the entire dwelling load.
- Sizing NM cable from the 75 °C column. NM cable stops at its 60 °C ampacity (334.80), whatever the terminals.
Method and verification
The calculator tries every size from the edition’s minimum (14 AWG copper and 12 AWG aluminum; 16 AWG copper on 10 A circuits in 2026) up to 2000 kcmil and keeps the first that passes every check. Ampacities, correction and adjustment factors, standard ratings and Table 250.122 come from the research data behind this site, checked value by value against at least two independent copies of each table. The 2026 additions for 16 AWG copper and 14 AWG copper-clad aluminum rest on a single NFPA draft, so any result that uses them carries a warning.
The tests reproduce Annex D Example D7 in both editions, hand-worked branch-circuit and feeder cases, the borderline EGC above, and the properties every answer must keep: a larger load, a hotter location, more conductors or a longer run never gives a smaller wire. Check the result against the edition your jurisdiction enforces; the NEC adoption map lists each state’s edition. For the drop alone, use the voltage drop calculator; for a single conductor’s ampacity, the ampacity calculator.
Updated 2026-10-14. Found a problem? Report it; every fix is logged publicly.