How to read the chart

The chart is in two parts. The first gives each conductor’s physical data: its area in circular mils and square millimetres, its bare diameter, its dc resistance and the nearest metric size. The second gives the ampacity the NEC assigns to the size in copper and in aluminum, the largest breaker that protects a copper conductor at its 75 °C rating, the largest dwelling service it can serve by the 83 % rule, and what the size is typically used for. The sizes run from the smallest to the largest, so the gauge numbers count down: 18 AWG first, then 16, 14 and so on to 1 AWG, then 1/0 (one-aught) to 4/0 (four-aught), then kcmil.

Ampacity comes in three columns because insulation comes in three temperature ratings. Use the column your conductor and its terminals can both take; for most breakers and panels that is 75 °C, and for circuits of 100 A or less with unmarked equipment it is 60 °C. Then correct for a hot location or a crowded raceway. The ampacity calculator does both.

Size, area, diameter and resistance

Bare conductor data from NEC Chapter 9, Table 8 (unchanged 2017–2026): area, diameter and dc resistance at 75 °C; the nearest IEC 60228 metric size is ours, by area.
SizeArea (cmil)Area (mm²)Diameter, solid (in)Diameter, stranded (in)Stranded (mm)Copper Ω/1000 ftAluminum Ω/1000 ftCopper Ω/kmNearest metric
18 AWG1,6200.8230.040.0461.177.9513.126.10.75 mm² (−9 %)
16 AWG2,5801.310.0510.0581.474.998.2116.41.5 mm² (+15 %)
14 AWG4,1102.080.0640.0731.853.145.1710.32.5 mm² (+20 %)
12 AWG6,5303.310.0810.0922.341.983.256.54 mm² (+21 %)
10 AWG10,3805.2610.1020.1162.951.242.044.076 mm² (+14 %)
8 AWG16,5108.3670.1280.1463.710.7781.282.5510 mm² (+20 %)
6 AWG26,24013.3—0.1844.670.4910.8081.6116 mm² (+20 %)
4 AWG41,74021.15—0.2325.890.3080.5081.0125 mm² (+18 %)
3 AWG52,62026.67—0.266.600.2450.4030.80425 mm² (−6 %)
2 AWG66,36033.62—0.2927.420.1940.3190.63635 mm² (+4 %)
1 AWG83,69042.41—0.3328.430.1540.2530.50550 mm² (+18 %)
1/0 AWG105,60053.49—0.3729.450.1220.2010.450 mm² (−7 %)
2/0 AWG133,10067.43—0.41810.620.09670.1590.31770 mm² (+4 %)
3/0 AWG167,80085.01—0.4711.940.07660.1260.25195 mm² (+12 %)
4/0 AWG211,600107.2—0.52813.410.06080.10.199120 mm² (+12 %)
250 kcmil250,000127—0.57514.600.05150.08470.169120 mm² (−6 %)
300 kcmil300,000152—0.6316.000.04290.07070.141150 mm² (−1 %)
350 kcmil350,000177—0.68117.300.03670.06050.12185 mm² (+5 %)
400 kcmil400,000203—0.72818.490.03210.05290.105185 mm² (−9 %)
500 kcmil500,000253—0.81320.650.02580.04240.0846240 mm² (−5 %)
600 kcmil600,000304—0.89322.680.02140.03530.0702300 mm² (−1 %)
700 kcmil700,000355—0.96424.490.01840.03030.0604400 mm² (+13 %)
750 kcmil750,000380—0.99825.350.01710.02820.0561400 mm² (+5 %)
800 kcmil800,000405—1.0326.160.01610.02650.0528400 mm² (−1 %)
900 kcmil900,000456—1.09427.790.01430.02350.0469500 mm² (+10 %)
1000 kcmil1,000,000507—1.15229.260.01290.02120.0423500 mm² (−1 %)
1250 kcmil1,250,000633—1.28932.740.01030.01690.0338630 mm² (−0 %)
1500 kcmil1,500,000760—1.41235.860.008580.01410.0281800 mm² (+5 %)
1750 kcmil1,750,000887—1.52638.760.007350.01210.0241800 mm² (−10 %)
2000 kcmil2,000,0001013—1.63241.450.006430.01060.02111,000 mm² (−1 %)

Sizes from 18 to 8 AWG are made solid as well as stranded, and the two have the same area but different diameters: the stranded conductor is wider because round strands leave gaps between them. Compact stranding is about 9 % smaller across than the Class B stranding shown here.

Ampacity chart for copper and aluminum

Ampacity in amperes from NEC Table 310.16 (2023; 2017: Table 310.15(B)(16)): not more than three current-carrying conductors, 30 °C (86 °F). The breaker and dwelling-service columns are calculated by our engine from the 75 °C copper value.
SizeCopperAluminum or CCALargest breaker, copper at 75 °CDwelling service, Cu / Al (310.12)Typical uses
60 °C75 °C90 °C60 °C75 °C90 °C
18 AWG——14———7 A—Fixture wire, doorbell, thermostat and control wiring
16 AWG——18———10 A—Fixture wire, cords and control wiring; 10 A lighting circuits from 2026
14 AWG152025———15 A—Lighting and general-purpose receptacle circuits
12 AWG20253015202520 A—Kitchen, bathroom, laundry and garage receptacle circuits
10 AWG30354025303530 A—Dryers, water heaters, smaller air conditioners
8 AWG40505535404550 A—Wall ovens, cooktops, smaller ranges
6 AWG55657540505570 A—Ranges, EV chargers, small subpanels
4 AWG70859555657590 A100 A / —Subpanel feeders and smaller services
3 AWG85100115657585100 A110 A / —Feeders and smaller services
2 AWG951151307590100125 A125 A / 100 AFeeders; aluminum dwelling services
1 AWG11013014585100115150 A150 A / 110 AFeeders and dwelling services
1/0 AWG125150170100120135150 A175 A / 125 ADwelling services and feeders
2/0 AWG145175195115135150175 A200 A / 150 ADwelling services and feeders
3/0 AWG165200225130155175200 A225 A / 175 ADwelling services and feeders
4/0 AWG195230260150180205250 A250 A / 200 ADwelling services and feeders
250 kcmil215255290170205230300 A300 A / 225 ALarger services and commercial feeders
300 kcmil240285320195230260300 A300 A / 250 ALarger services and commercial feeders
350 kcmil260310350210250280350 A350 A / 300 ALarger services and commercial feeders
400 kcmil280335380225270305350 A400 A / 300 ALarger services and commercial feeders
500 kcmil320380430260310350400 A400 A / 350 ALarger services and commercial feeders
600 kcmil350420475285340385450 A400 A / 400 ACommercial services and feeders, often in parallel sets
700 kcmil385460520315375425500 A400 A / 400 ACommercial services and feeders, often in parallel sets
750 kcmil400475535320385435500 A400 A / 400 ACommercial services and feeders, often in parallel sets
800 kcmil410490555330395445500 A400 A / 400 ACommercial services and feeders, often in parallel sets
900 kcmil435520585355425480600 A400 A / 400 ACommercial services and feeders, often in parallel sets
1000 kcmil455545615375445500600 A400 A / 400 ACommercial services and feeders, often in parallel sets
1250 kcmil495590665405485545600 A400 A / 400 ACommercial services and feeders, often in parallel sets
1500 kcmil525625705435520585700 A400 A / 400 ACommercial services and feeders, often in parallel sets
1750 kcmil545650735455545615700 A400 A / 400 ACommercial services and feeders, often in parallel sets
2000 kcmil555665750470560630700 A400 A / 400 ACommercial services and feeders, often in parallel sets

A dash means the table lists no value: aluminum is not used below 12 AWG, and 18 and 16 AWG copper appear only in the 90 °C column, for special uses. The 2026 NEC adds 16 AWG copper at 10 A in the 60 °C column and 14 AWG copper-clad aluminum at 10 A, deletes the 18 AWG row, and keeps the 18 and 16 AWG 90 °C values only for Types MI and MTW. Those 2026 changes come from a single NFPA draft that we have not yet checked against the printed book, so the chart shows the 2023 values and our calculators warn whenever a 2026 result depends on them.

Every size to scale

Conductor cross-sections to scaleEvery size from 18 AWG to 2000 kcmil drawn at one scale. The filled disc is the metal area; the dashed ring is the overall diameter of Class B stranding. 2000 kcmil has 1,235 times the area of 18 AWG and 35 times the diameter.18161412108643211/02/03/04/025030035040050060070075080090010001250150017502000
All 30 sizes at one scale, AWG sizes labelled by gauge and kcmil sizes by thousands of circular mils. Filled: metal area. Dashed: overall diameter of Class B stranding from Chapter 9, Table 8, a little larger because round strands leave gaps.

Reading the typical-uses column

The uses column describes where each size usually turns up in buildings, not what a particular circuit needs. Two things move a real circuit away from the typical size. Conditions of use can push it up: a hot attic, a crowded conduit, a sunny roof or a long run all call for a larger conductor than the chart’s first match. Specific articles can push it down or sideways: motor and air-conditioning circuits are protected by breakers much larger than the wire’s ampacity, because the motor rules provide overload protection separately. The breaker column applies the general rule only, with the next-size-up allowance of 240.4(B) and the small-conductor limits of 240.4(D).

Solid or stranded

Solid conductors are cheaper, hold their shape under a terminal screw and are the norm in 14 to 10 AWG building cable. Stranded conductors bend more easily, survive vibration and pull far better through conduit, which is why larger building wire is almost always stranded: conductors 8 AWG and larger installed in raceways must be stranded unless another rule allows solid (310.3(C) in the 2020 and 2023 editions). Stranding does not change the ampacity, and the two constructions have the same nominal area. It does change the diameter, and slightly the resistance: 12 AWG solid copper is 1.93 Ω per 1000 ft and 7-strand 12 AWG is 1.98 Ω, because each strand is twisted and slightly longer than the cable.

Insulation and the overall diameter

The diameters here are for the bare metal. The finished wire is larger by twice the insulation thickness, which depends on the type: THHN’s thin nylon-jacketed insulation adds the least, while XHHW, RHW and USE add more. That difference is what decides how many conductors fit in a conduit, so raceway fill uses the insulated diameters of Chapter 9, Table 5 rather than this chart. For bare conductors, such as a bare equipment grounding conductor in a raceway, the 2026 edition says plainly that the Table 8 dimensions apply.

How the AWG sizes work

American Wire Gauge is a geometric series. It fixes 36 AWG at 0.005 in. and 4/0 at 0.46 in., a ratio of 92, and spaces 39 gauges between them, so each gauge is 1.1229 times the diameter of the next smaller one and 1.261 times its area. That gives the rules of thumb electricians use:

  • Three gauges double the area: 3 AWG has 2.01 times the area of 6 AWG.
  • Six gauges double the diameter and quadruple the area: 4 AWG has 4.02 times the area of 10 AWG.
  • Ten gauges multiply the area by about ten: 4 AWG has 10.2 times the area of 14 AWG.

Because resistance falls in proportion to area, the same rules apply to resistance in reverse: going up three sizes roughly halves the voltage drop. Past 4/0 the gauge numbers run out, and conductors are named by area directly: 250, 300, 350 kcmil and up, in thousands of circular mils. Electricians often write the older “MCM” for the same thing.

Circular mils and square millimetres

A circular mil is the area of a circle one mil (a thousandth of an inch) in diameter. It makes the arithmetic of round wire easy: a solid conductor d mils across has an area of d² circular mils, with no π to carry. 10 AWG solid is 102 mils across and 10,380 cmil. To convert, 1 mm² = 1,973.5 cmil, so divide circular mils by 1,973.5 for square millimetres. The NEC’s own tables use circular mils for voltage-drop and grounding calculations, which is why the proportional grounding-conductor rule and the K-factor voltage drop formula both work in cmil.

Resistance and voltage drop

The resistance column is the Chapter 9 value at 75 °C, the temperature the NEC assumes for voltage-drop work. Copper and aluminum both get about 0.32 % more resistive per degree of temperature rise, so a lightly loaded conductor running cooler drops a little less than the table suggests. Multiply the resistance by twice the one-way length for a two-wire circuit, or use the voltage drop calculator, which also handles three-phase circuits, ac reactance from Chapter 9, Table 9, and the IEC and BS 7671 methods.

Using the ampacity columns safely

The ampacity chart is a starting point, not the answer for a circuit. Table 310.16 assumes a 30 °C (86 °F) ambient and no more than three current-carrying conductors in the raceway or cable; correct for anything hotter or more crowded. Size the circuit for 125 % of any continuous load, check that the terminals allow the column you used, and remember that 14, 12 and 10 AWG are capped at 15, 20 and 30 A by 240.4(D) in copper. A dwelling service may use the 83 % rule of 310.12, which is what the dwelling column shows. The wire size calculator applies all of these rules, edition by edition, and the ground wire size calculator sizes the equipment grounding conductor that goes with it.

Metric equivalents

Metric cables follow IEC 60228, a separate series of nominal areas: 1.5, 2.5, 4, 6, 10, 16 mm² and so on. No AWG size matches one exactly. 14 AWG (2.08 mm²) sits between 1.5 and 2.5 mm², and 12 AWG (3.31 mm²) sits 17 % below 4 mm². The chart lists the nearest size by area ratio, with the difference in brackets. Treat it as a guide to what a metric equivalent looks like, not as a substitution rule: a metric cable is sized from its own current-carrying capacity tables (IEC 60364-5-52 or BS 7671 Appendix 4) for its installation method.

Look up a size under your conditions

Choose a size, insulation, ambient temperature and number of conductors to see the usable ampacity and the largest breaker for your installation: