electrician.wiki

Electrical calculators

Amps to watts calculator

Watts = amps × volts. On AC, multiply by the power factor too, and for three-phase by √3 as well. Enter the current and the voltage to get watts, kilowatts and volt-amperes, with every step shown.

New to this? Power factor explained

Report a problem with this result

How to convert amps to watts

To convert amps to watts, multiply the current by the voltage: watts = amps × volts. That gives the exact answer for DC and for resistive AC loads. For other AC loads multiply by the power factor as well, and for three-phase by √3 too.

  1. Measure or read the current in amps. For milliamps, divide by 1,000.
  2. Find the voltage: 5 V for USB, 12 or 24 V for vehicles, 120 or 240 V in North America, 230 V in most other countries.
  3. Multiply amps by volts. For an AC motor or electronic load, multiply by its power factor too.
  4. For a balanced three-phase load, multiply by √3 (about 1.732) as well, with the line-to-line voltage.

So 10 amps is 10 × 120 = 1,200 W on a 120 V circuit and 2,300 W at 230 V. A USB charger rated 2.4 A at 5 V delivers 12 W.

How to use the amps to watts calculator

This amps to watts calculator turns a current into power for DC, single-phase AC and three-phase AC circuits. It gives the real power in watts and kilowatts and, for AC, the apparent power in volt-amperes, which is what the cable, breaker and transformer actually carry. The working is shown under every result.

  1. System. DC for batteries, solar strings and DC drives. Single-phase AC for ordinary 120, 230 or 240 V circuits, including a 208 V load connected between two phases. Three-phase AC for motors, rooftop units and feeders.
  2. Current. For three-phase, the current in one line of a balanced load. A clamp-meter reading and a nameplate figure both work, but they answer different questions (see the mistakes below).
  3. Voltage. For three-phase, say whether the figure is line-to-line (208, 400, 480 V) or line-to-neutral (120, 230, 277 V). The calculator flags the common mix-ups.
  4. Power factor (AC only). Leave it at 1 for heaters, kettles and incandescent lamps. Induction motors run at about 0.8 to 0.9 at full load and well below that when lightly loaded. Electronic loads with power-factor correction are usually 0.9 or better; small LED lamps and chargers without it can be much lower.

Amps to watts formulas

Power is voltage times current. For DC that is the whole story. On AC, voltage times current gives the apparent power in volt-amperes; multiplying by the power factor gives the real power in watts, the part that becomes heat, light or shaft work.

DC

P=V·I

Single-phase AC

P=V·I·PF

Three-phase AC (balanced)

P=3·VLL·I·PF=3·VLN·I·PF

Apparent power, single-phase and three-phase

S=V·I
S=3·VLL·I

The √3 is not magic. Each phase of a balanced load delivers VLN·I·PF, so three phases deliver three times that. The line-to-line voltage is √3 times the line-to-neutral voltage (√3 × 277 V = 479.8 V, the nominal 480 V), so the same total can be written with √3 and the line-to-line voltage. Both forms give the same answer as long as each is paired with its own voltage. Divide watts by 1,000 for kilowatts.

Worked examples

Baseboard heaters on a 120 V circuit

A clamp meter reads 15 A on a 120 V circuit feeding resistance heaters. Resistance heating has a power factor of 1.
  1. 1. Real power

    P=V·I·PF=120V·15A·1=1,800W
  2. 2. Apparent power (what the wiring carries)

    S=V·I=120V·15A=1,800VA
  3. 3. In kilowatts

    P=1,800W1,000=1.8kW

15 A at 120 V single-phase is 1,800 W (1.8 kW).

A heat pump outdoor unit on 240 V

The unit measures 18.5 A at 240 V, and the compressor runs at a power factor of about 0.9 at this load.
  1. 1. Real power

    P=V·I·PF=240V·18.5A·0.9=3,996W
  2. 2. Apparent power (what the wiring carries)

    S=V·I=240V·18.5A=4,440VA
  3. 3. In kilowatts

    P=3,996W1,000=3.996kW

18.5 A at 240 V single-phase with power factor 0.9 is 3,996 W (3.996 kW); the apparent power is 4.44 kVA.

Line-to-neutral readings on a 208Y/120 V panel

You measured 120 V from each phase to neutral and 40 A in each line of a three-phase load. Choosing line-to-neutral saves converting to 208 V first, and gives the same answer.
  1. 1. Real power (line-to-neutral voltage)

    P=3·VLN·I·PF=3·120V·40A·0.95=13,680W
  2. 2. Apparent power (what the wiring carries)

    S=3·VLN·I=3·120V·40A=14,400VA
  3. 3. In kilowatts

    P=13,680W1,000=13.68kW

40 A per line at 120 V line-to-neutral (207.8 V line-to-line) three-phase with power factor 0.95 is 13,680 W (13.68 kW); the apparent power is 14.4 kVA.

A 480 V three-phase air handler

The fan motor draws 42 A per line at 480 V with a power factor of 0.88.
  1. 1. Real power (line-to-line voltage)

    P=3·VLL·I·PF=3·480V·42A·0.88=30,728W
  2. 2. Apparent power (what the wiring carries)

    S=3·VLL·I=3·480V·42A=34,918VA
  3. 3. In kilowatts

    P=30,728W1,000=30.73kW

42 A per line at 480 V three-phase with power factor 0.88 is 30,728 W (30.73 kW); the apparent power is 34.92 kVA.

A kettle on 230 V

A UK kettle drawing 13 A, the rating of its plug fuse. The element is resistive, so the power factor is 1.
  1. 1. Real power

    P=V·I·PF=230V·13A·1=2,990W
  2. 2. Apparent power (what the wiring carries)

    S=V·I=230V·13A=2,990VA
  3. 3. In kilowatts

    P=2,990W1,000=2.99kW

13 A at 230 V single-phase is 2,990 W (2.99 kW).

A 400 V three-phase motor

A motor drawing 28 A per line at 400 V and power factor 0.86. This is electrical input; at about 90 % efficiency the shaft delivers roughly 15 kW.
  1. 1. Real power (line-to-line voltage)

    P=3·VLL·I·PF=3·400V·28A·0.86=16,683W
  2. 2. Apparent power (what the wiring carries)

    S=3·VLL·I=3·400V·28A=19,399VA
  3. 3. In kilowatts

    P=16,683W1,000=16.68kW

28 A per line at 400 V three-phase with power factor 0.86 is 16,683 W (16.68 kW); the apparent power is 19.4 kVA.

Amps to watts conversion chart

These figures come from the same engine as the calculator. For a motor or other inductive load, multiply by its power factor. To go the other way, from a wattage to amps, use the watts to amps calculator.

Real power in watts at power factor 1. Three-phase columns use line-to-line voltage and the current in each line.
Amps12 V DC120 V 1-phase230 V 1-phase240 V 1-phase208 V 3-phase400 V 3-phase480 V 3-phase
1 A12120230240360.3692.8831.4
5 A606001,1501,2001,8013,4644,157
10 A1201,2002,3002,4003,6036,9288,314
15 A1801,8003,4503,6005,40410,39212,471
20 A2402,4004,6004,8007,20513,85616,628
30 A3603,6006,9007,20010,80820,78524,942
40 A4804,8009,2009,60014,41127,71333,255
50 A6006,00011,50012,00018,01334,64141,569
60 A7207,20013,80014,40021,61641,56949,883
100 A1,20012,00023,00024,00036,02769,28283,138

Amps to watts at 5, 12, 24 and 48 V DC

Battery, solar and USB ratings are usually given in amps, while loads are given in watts. On DC there is no power factor, so the conversion is a single multiplication. Remember that a battery’s voltage sags as it discharges, so the current for a fixed wattage rises towards the end.

Watts = amps × volts for DC. 5 V is USB; 12, 24 and 48 V are vehicle, solar and battery systems.
Amps5 V DC12 V DC24 V DC48 V DC
0.5 A2.561224
1 A5122448
2 A10244896
2.4 A1228.857.6115.2
3 A153672144
5 A2560120240
10 A50120240480
20 A100240480960
50 A2506001,2002,400
100 A5001,2002,4004,800

How many watts can a circuit carry?

Multiply the breaker rating by the voltage for the most a circuit can deliver, and use 80 % of that for anything that runs for three hours or more. These figures assume power factor 1; motor loads deliver fewer watts for the same current.

Watts at the breaker rating and at 80 % of it (a continuous load under the NEC), power factor 1.
Breaker120 V, full120 V, 80 %240 V, full240 V, 80 %
15 A1,8001,4403,6002,880
20 A2,4001,9204,8003,840
30 A3,6002,8807,2005,760
40 A4,8003,8409,6007,680
50 A6,0004,80012,0009,600
60 A7,2005,76014,40011,520

Mistakes that throw the answer off

  • Leaving the power factor at 1 for a motor. 10 A at 240 V is 2,400 W for a heater but 1,920 W for a motor at power factor 0.8. Using 1 overstates the motor’s real power by 25 %.
  • Pairing the wrong three-phase voltage with the formula. Using 277 V with √3 understates the power by 42 %; using 480 V with the factor 3 overstates it by 73 %. If you are not sure which voltage you have, the three-phase power calculator explains line and phase values for wye and delta systems.
  • Treating a 208 V single-phase load as three-phase. A water heater or condenser connected between two legs of a 208Y/120 V system is a single-phase load: P = 208 V × I × PF, with no √3.
  • Reading the nameplate as running current. Motor full-load amps are the current at full rated load. Air-conditioning nameplates list RLA and MCA, and MCA already includes 125 % of the largest motor for wire sizing. For energy use, measure under real load.
  • Measuring electronic loads with an average-responding meter. LED drivers, drives and switch-mode supplies draw distorted current that such meters misread. Use a true-RMS clamp for amps and a power meter if you need real watts.
  • Confusing input and output. The result is electrical input power. A motor’s horsepower or kW rating is the shaft output (1 hp = 746 W), which is lower by the motor’s efficiency.

Continuous loads and the 80 % figure

A 20 A circuit at 120 V carries 2,400 W at its full rating. A load that runs for three hours or more is a continuous load, and the NEC sizes the conductors and breaker for 125 % of it (210.19(A)(1) and 210.20(A)). Turned around, a continuous load may use only 80 % of the breaker: 16 A, which is 1,920 W at 120 V or 3,840 W at 240 V. When you are planning a circuit rather than measuring one, start from the wattage with the watts to amps calculator, size the conductor with the wire size calculator (or the IEC cable size calculator), and check long runs with the voltage drop calculator. For a transformer feeding the load, the transformer calculator gives full-load amps by kVA.

Method and verification

The calculator evaluates P=k·V·I·PF, where k is 1 for DC and single-phase, √3 for three-phase with line-to-line voltage and 3 with line-to-neutral voltage. DC ignores the power factor. Apparent power is the same product without the power factor. Everything is computed in double precision and rounded only for display: watts to the nearest watt from 1,000 W up and to four significant figures below that; kilowatts, kVA and volts to four significant figures.

The tests check eight cases worked by hand, from 10 A at 12 V DC to 100 A at 480 V and power factor 0.85 (70,668 W). They also check that line-to-neutral and line-to-line entries for the same system agree, that a round trip through the watts to amps calculator returns the starting current, and that zero, negative and out-of-range inputs are refused rather than answered. The underlying relationships are the ones in the Ohm’s law calculator, extended with the power factor for AC.

Assumes RMS values, a balanced three-phase load and the true power factor. Updated 2026-10-14. Found a problem? Report it and we log every fix publicly.

Questions people ask

How many watts is 1 amp?
120 W at 120 V, 230 W at 230 V and 240 W at 240 V. At 12 V DC it is 12 W, and at 5 V (USB) 5 W: watts are always amps times volts.
How many watts is 2.4 amps?
On a 5 V USB port, 12 W. At 12 V it is 28.8 W, and at 120 V 288 W.
How many watts is 10 amps?
1,200 W at 120 V, 2,300 W at 230 V and 2,400 W at 240 V, for a resistive load.
How many watts is 15 amps at 120 volts?
1,800 W for a resistive load such as a heater (15 A × 120 V). For a motor at power factor 0.8 the real power is 1,440 W, although the circuit still carries 1,800 VA.
How do I convert amps to watts for three-phase?
Multiply √3 (about 1.732) by the line-to-line voltage, the current in each line and the power factor. 100 A at 480 V and power factor 0.85 is 70,668 W, or 70.67 kW. With a line-to-neutral voltage, use 3 instead of √3.
Why does the power factor matter when converting amps to watts?
Because on AC, volts times amps gives volt-amperes, not watts. Motors and other inductive loads draw current that is partly out of step with the voltage; that part heats the wiring but does no work. The power factor is the share of the volt-amperes that is real power.
How many watts can a 20 amp circuit handle?
At 120 V, 2,400 W at the breaker’s full rating, or 1,920 W for a load that runs three hours or more (80 % of the rating). At 240 V the figures are 4,800 W and 3,840 W.
Are watts and volt-amperes the same?
Only when the power factor is 1, as with heaters and incandescent lamps. For anything else, volt-amperes are larger than watts. Generators, UPS units and transformers are rated in VA or kVA because their limit is current, whatever the power factor.