Amps to watts calculator
Watts = amps × volts. On AC, multiply by the power factor too, and for three-phase by √3 as well. Enter the current and the voltage to get watts, kilowatts and volt-amperes, with every step shown.
Calculated with electrician.wiki · https://electrician.wiki/calculators/amps-to-watts/
New to this? Power factor explained
Report a problem with this result
How to convert amps to watts
To convert amps to watts, multiply the current by the voltage: watts = amps × volts. That gives the exact answer for DC and for resistive AC loads. For other AC loads multiply by the power factor as well, and for three-phase by √3 too.
- Measure or read the current in amps. For milliamps, divide by 1,000.
- Find the voltage: 5 V for USB, 12 or 24 V for vehicles, 120 or 240 V in North America, 230 V in most other countries.
- Multiply amps by volts. For an AC motor or electronic load, multiply by its power factor too.
- For a balanced three-phase load, multiply by √3 (about 1.732) as well, with the line-to-line voltage.
So 10 amps is 10 × 120 = 1,200 W on a 120 V circuit and 2,300 W at 230 V. A USB charger rated 2.4 A at 5 V delivers 12 W.
How to use the amps to watts calculator
This amps to watts calculator turns a current into power for DC, single-phase AC and three-phase AC circuits. It gives the real power in watts and kilowatts and, for AC, the apparent power in volt-amperes, which is what the cable, breaker and transformer actually carry. The working is shown under every result.
- System. DC for batteries, solar strings and DC drives. Single-phase AC for ordinary 120, 230 or 240 V circuits, including a 208 V load connected between two phases. Three-phase AC for motors, rooftop units and feeders.
- Current. For three-phase, the current in one line of a balanced load. A clamp-meter reading and a nameplate figure both work, but they answer different questions (see the mistakes below).
- Voltage. For three-phase, say whether the figure is line-to-line (208, 400, 480 V) or line-to-neutral (120, 230, 277 V). The calculator flags the common mix-ups.
- Power factor (AC only). Leave it at 1 for heaters, kettles and incandescent lamps. Induction motors run at about 0.8 to 0.9 at full load and well below that when lightly loaded. Electronic loads with power-factor correction are usually 0.9 or better; small LED lamps and chargers without it can be much lower.
Amps to watts formulas
Power is voltage times current. For DC that is the whole story. On AC, voltage times current gives the apparent power in volt-amperes; multiplying by the power factor gives the real power in watts, the part that becomes heat, light or shaft work.
DC
Single-phase AC
Three-phase AC (balanced)
Apparent power, single-phase and three-phase
The √3 is not magic. Each phase of a balanced load delivers , so three phases deliver three times that. The line-to-line voltage is √3 times the line-to-neutral voltage (√3 × 277 V = 479.8 V, the nominal 480 V), so the same total can be written with √3 and the line-to-line voltage. Both forms give the same answer as long as each is paired with its own voltage. Divide watts by 1,000 for kilowatts.
Worked examples
Baseboard heaters on a 120 V circuit
1. Real power
2. Apparent power (what the wiring carries)
3. In kilowatts
15 A at 120 V single-phase is 1,800 W (1.8 kW).
A heat pump outdoor unit on 240 V
1. Real power
2. Apparent power (what the wiring carries)
3. In kilowatts
18.5 A at 240 V single-phase with power factor 0.9 is 3,996 W (3.996 kW); the apparent power is 4.44 kVA.
Line-to-neutral readings on a 208Y/120 V panel
1. Real power (line-to-neutral voltage)
2. Apparent power (what the wiring carries)
3. In kilowatts
40 A per line at 120 V line-to-neutral (207.8 V line-to-line) three-phase with power factor 0.95 is 13,680 W (13.68 kW); the apparent power is 14.4 kVA.
A 480 V three-phase air handler
1. Real power (line-to-line voltage)
2. Apparent power (what the wiring carries)
3. In kilowatts
42 A per line at 480 V three-phase with power factor 0.88 is 30,728 W (30.73 kW); the apparent power is 34.92 kVA.
A kettle on 230 V
1. Real power
2. Apparent power (what the wiring carries)
3. In kilowatts
13 A at 230 V single-phase is 2,990 W (2.99 kW).
A 400 V three-phase motor
1. Real power (line-to-line voltage)
2. Apparent power (what the wiring carries)
3. In kilowatts
28 A per line at 400 V three-phase with power factor 0.86 is 16,683 W (16.68 kW); the apparent power is 19.4 kVA.
Amps to watts conversion chart
These figures come from the same engine as the calculator. For a motor or other inductive load, multiply by its power factor. To go the other way, from a wattage to amps, use the watts to amps calculator.
| Amps | 12 V DC | 120 V 1-phase | 230 V 1-phase | 240 V 1-phase | 208 V 3-phase | 400 V 3-phase | 480 V 3-phase |
|---|---|---|---|---|---|---|---|
| 1 A | 12 | 120 | 230 | 240 | 360.3 | 692.8 | 831.4 |
| 5 A | 60 | 600 | 1,150 | 1,200 | 1,801 | 3,464 | 4,157 |
| 10 A | 120 | 1,200 | 2,300 | 2,400 | 3,603 | 6,928 | 8,314 |
| 15 A | 180 | 1,800 | 3,450 | 3,600 | 5,404 | 10,392 | 12,471 |
| 20 A | 240 | 2,400 | 4,600 | 4,800 | 7,205 | 13,856 | 16,628 |
| 30 A | 360 | 3,600 | 6,900 | 7,200 | 10,808 | 20,785 | 24,942 |
| 40 A | 480 | 4,800 | 9,200 | 9,600 | 14,411 | 27,713 | 33,255 |
| 50 A | 600 | 6,000 | 11,500 | 12,000 | 18,013 | 34,641 | 41,569 |
| 60 A | 720 | 7,200 | 13,800 | 14,400 | 21,616 | 41,569 | 49,883 |
| 100 A | 1,200 | 12,000 | 23,000 | 24,000 | 36,027 | 69,282 | 83,138 |
Amps to watts at 5, 12, 24 and 48 V DC
Battery, solar and USB ratings are usually given in amps, while loads are given in watts. On DC there is no power factor, so the conversion is a single multiplication. Remember that a battery’s voltage sags as it discharges, so the current for a fixed wattage rises towards the end.
| Amps | 5 V DC | 12 V DC | 24 V DC | 48 V DC |
|---|---|---|---|---|
| 0.5 A | 2.5 | 6 | 12 | 24 |
| 1 A | 5 | 12 | 24 | 48 |
| 2 A | 10 | 24 | 48 | 96 |
| 2.4 A | 12 | 28.8 | 57.6 | 115.2 |
| 3 A | 15 | 36 | 72 | 144 |
| 5 A | 25 | 60 | 120 | 240 |
| 10 A | 50 | 120 | 240 | 480 |
| 20 A | 100 | 240 | 480 | 960 |
| 50 A | 250 | 600 | 1,200 | 2,400 |
| 100 A | 500 | 1,200 | 2,400 | 4,800 |
How many watts can a circuit carry?
Multiply the breaker rating by the voltage for the most a circuit can deliver, and use 80 % of that for anything that runs for three hours or more. These figures assume power factor 1; motor loads deliver fewer watts for the same current.
| Breaker | 120 V, full | 120 V, 80 % | 240 V, full | 240 V, 80 % |
|---|---|---|---|---|
| 15 A | 1,800 | 1,440 | 3,600 | 2,880 |
| 20 A | 2,400 | 1,920 | 4,800 | 3,840 |
| 30 A | 3,600 | 2,880 | 7,200 | 5,760 |
| 40 A | 4,800 | 3,840 | 9,600 | 7,680 |
| 50 A | 6,000 | 4,800 | 12,000 | 9,600 |
| 60 A | 7,200 | 5,760 | 14,400 | 11,520 |
Mistakes that throw the answer off
- Leaving the power factor at 1 for a motor. 10 A at 240 V is 2,400 W for a heater but 1,920 W for a motor at power factor 0.8. Using 1 overstates the motor’s real power by 25 %.
- Pairing the wrong three-phase voltage with the formula. Using 277 V with √3 understates the power by 42 %; using 480 V with the factor 3 overstates it by 73 %. If you are not sure which voltage you have, the three-phase power calculator explains line and phase values for wye and delta systems.
- Treating a 208 V single-phase load as three-phase. A water heater or condenser connected between two legs of a 208Y/120 V system is a single-phase load: P = 208 V × I × PF, with no √3.
- Reading the nameplate as running current. Motor full-load amps are the current at full rated load. Air-conditioning nameplates list RLA and MCA, and MCA already includes 125 % of the largest motor for wire sizing. For energy use, measure under real load.
- Measuring electronic loads with an average-responding meter. LED drivers, drives and switch-mode supplies draw distorted current that such meters misread. Use a true-RMS clamp for amps and a power meter if you need real watts.
- Confusing input and output. The result is electrical input power. A motor’s horsepower or kW rating is the shaft output (1 hp = 746 W), which is lower by the motor’s efficiency.
Continuous loads and the 80 % figure
A 20 A circuit at 120 V carries 2,400 W at its full rating. A load that runs for three hours or more is a continuous load, and the NEC sizes the conductors and breaker for 125 % of it (210.19(A)(1) and 210.20(A)). Turned around, a continuous load may use only 80 % of the breaker: 16 A, which is 1,920 W at 120 V or 3,840 W at 240 V. When you are planning a circuit rather than measuring one, start from the wattage with the watts to amps calculator, size the conductor with the wire size calculator (or the IEC cable size calculator), and check long runs with the voltage drop calculator. For a transformer feeding the load, the transformer calculator gives full-load amps by kVA.
Method and verification
The calculator evaluates , where k is 1 for DC and single-phase, √3 for three-phase with line-to-line voltage and 3 with line-to-neutral voltage. DC ignores the power factor. Apparent power is the same product without the power factor. Everything is computed in double precision and rounded only for display: watts to the nearest watt from 1,000 W up and to four significant figures below that; kilowatts, kVA and volts to four significant figures.
The tests check eight cases worked by hand, from 10 A at 12 V DC to 100 A at 480 V and power factor 0.85 (70,668 W). They also check that line-to-neutral and line-to-line entries for the same system agree, that a round trip through the watts to amps calculator returns the starting current, and that zero, negative and out-of-range inputs are refused rather than answered. The underlying relationships are the ones in the Ohm’s law calculator, extended with the power factor for AC.
Assumes RMS values, a balanced three-phase load and the true power factor. Updated 2026-10-14. Found a problem? Report it and we log every fix publicly.