IEC & BS 7671 calculators
Prospective fault current calculator
Turn loop impedance readings into prospective short-circuit and earth fault currents, estimate three-phase levels, and check the breaking capacity of the protective devices.
Calculated with electrician.wiki · https://electrician.wiki/calculators/prospective-fault-current/
Report a problem with this result
How to use the prospective fault current calculator
Enter the two loop impedances a loop tester measures at the point you care about, usually the origin: Z(L–N), between line and neutral, and the earth fault loop impedance, which at the origin is Ze. The calculator turns each into a current at the nominal voltage, takes the larger as the prospective fault current (PFC), and checks it against the breaking capacity of the device you choose. For a three-phase supply it estimates the three-phase fault from the single-phase reading. In BS 7671 mode you can skip the readings and use the UK design values instead.
PSCC, PEFC and PFC
A bolted fault between line and neutral drives the prospective short-circuit current (PSCC); a fault from line to earth drives the prospective earth fault current (PEFC). Each is the voltage divided by the impedance of its loop:
The prospective fault current you record and design for is the larger of the two. On a TN-C-S supply they are often close; on a TN-S supply the earth path through the cable sheath usually makes the PEFC smaller; on a TT supply the PEFC is tiny. With the default readings, 0.24 Ω and 0.35 Ω, the PSCC is 958 A and the PEFC 657 A. Most loop testers display exactly this: the nominal voltage over the measured impedance.
Why it matters: breaking capacity
Every device that may have to interrupt a fault must be able to break the largest current that can flow where it is installed (BS 7671 Regulation 434.5.1). Beyond that rating, a breaker’s contacts can weld or the case can rupture. Circuit-breakers to BS EN 60898 show their rated short-circuit capacity Icn in a box, in amperes: 6000 for 6 kA, 10000 for 10 kA. Some also quote a service capacity Ics, the level after which the breaker is still fit for use, which can be lower.
UK consumer units add a twist. A consumer unit to BS EN 61439-3 is designed as an assembly, with its devices and outer enclosure, to withstand a prospective fault current of up to 16 kA in domestic and similar premises (NICEIC). That conditional rating is why 6 kA breakers are normal in a house whose supply could deliver more than 6 kA. With the UK design value of 16 kA, a 6 kA breaker on its own fails the check, while the same breaker in a 16 kA consumer unit passes.
Typical UK supplies
UK distributors declare the most Ze their supplies will present, and the IET recommends designing with those figures from the Energy Networks Association’s Engineering Recommendation P23. For the prospective short-circuit current the IET recommends assuming 16 kA at the origin of a single-phase supply up to 100 A where the service cable is longer than 2 m, unless the distributor gives a different figure. Measure on site whenever you can: real values are usually lower, but an installation near a substation can be higher.
| Earthing | Typical max Ze | PEFC at 230 V | Note |
|---|---|---|---|
| TN-C-S (PME) | 0.35 Ω | 657 A | combined neutral and earth in the supply cable |
| TN-S | 0.8 Ω | 288 A | separate earth, usually the cable sheath |
| TT | 21 Ω | 11 A | distributor’s part only; your earth electrode adds to it |
Three-phase supplies: × 2 or × √3?
A single-phase loop tester measures one line and the neutral. Splitting that loop into the line path ZL (transformer winding plus line conductor) and the neutral path ZN, the reading and the three kinds of fault are:
If the neutral path has the same impedance as the line path, the symmetrical three-phase fault is exactly twice the line–neutral reading, and a line-to-line fault is √3 times it, which is (√3/2) ≈ 0.87 of the three-phase value, the relation IEC 60909-0 gives. The IET On-Site Guide takes the first, simpler route: double the single-phase reading for a three-phase supply. It usually errs high, because the neutral path doesn’t include the transformer winding, so ZN is smaller than ZL. Multiplying by √3 instead answers a different question, the line-to-line fault, and understates the worst case by about 13 %. A reduced or very long neutral reverses the margin, so measure between lines where you can.
Voltage factors: cmax and cmin
The supply isn’t always at exactly 230 V. IEC 60909-0, the standard for short-circuit calculations, scales the voltage with a factor c: for low-voltage networks, cmax = 1.10 where the voltage may run 10 % high (1.05 for a 6 % tolerance) when you want the largest current, and cmin = 0.95 when you want the smallest. In IEC mode the calculator applies cmax to the breaking-capacity check; our data has those cmax figures from a single source, so the result says so. BS 7671 practice compares the value at nominal voltage, and the UK design value is already a maximum. The minimum earth fault current, cmin × U0 / Ze, is the figure that matters for disconnection: 624 A for the default readings, which you can carry into the earth fault loop impedance calculator.
Worked examples
Readings at a consumer unit
1. Prospective short-circuit current (line–neutral)
2. Prospective earth fault current (line–earth)
3. Highest fault current the devices must break
4. Breaking capacity is enough
5. Minimum earth fault current (for disconnection checks)
With Z(L–N) = 0.24 Ω and an earth loop of 0.35 Ω, the prospective short-circuit current is 958 A and the earth fault current 657 A. The 958 A maximum is within the 6 kA breaking capacity.
Designing without readings
1. Short-circuit current (UK design value)
PSCC = 16 kA
2. Earth fault current with the typical TN-C-S Ze
3. Highest fault current the devices must break
4. Breaking capacity is enough
5. Minimum earth fault current (for disconnection checks)
For design, a UK single-phase supply up to 100 A is taken as 16 kA, so devices need a 16 kA rating or more: this one qualifies. The earth fault current with a typical TN-C-S Ze of 0.35 Ω is 657 A.
A three-phase board near a substation
1. Prospective short-circuit current (line–neutral)
2. Prospective earth fault current (line–earth)
3. Three-phase fault, estimated from the single-phase reading
4. Highest fault current the devices must break
5. Breaking capacity is enough
6. Minimum earth fault current (for disconnection checks)
With Z(L–N) = 0.05 Ω and an earth loop of 0.12 Ω, the prospective short-circuit current is 4.6 kA and the earth fault current 1.92 kA; a three-phase fault could reach about 9.2 kA. The 9.2 kA maximum is within the 10 kA breaking capacity.
The IEC 60909 maximum
1. Prospective short-circuit current (line–neutral)
2. Prospective earth fault current (line–earth)
3. Maximum fault current with cmax = 1.10 (IEC 60909-0)
4. Breaking capacity is enough
5. Minimum earth fault current (for disconnection checks)
With Z(L–N) = 0.24 Ω and an earth loop of 0.35 Ω, the prospective short-circuit current is 958 A and the earth fault current 657 A. The 1.05 kA maximum is within the 6 kA breaking capacity.
Common mistakes
- Recording only the earth fault current. The PFC is the larger of PSCC and PEFC; on many supplies that is the short-circuit value.
- Using √3 for a three-phase supply. That gives the line-to-line fault; the three-phase fault is larger. At the default reading the difference is 257 A.
- Checking 6 kA breakers against 16 kA without the consumer unit’s rating. The conditional rating belongs to the tested assembly, not to loose devices in a different enclosure.
- Measuring away from the device. PFC falls along a circuit; a distribution board 30 m from the origin sees less than the origin.
- Adding a voltage factor to a design value. The distributor’s or the IET’s figure is already a maximum.
The three-phase example above, at 9.2 kA, would exceed 6 kA devices but suits 10 kA ones. Size the cables with the cable size calculator and check that their protective conductors survive the fault with the cpc size calculator. The US equivalent of this calculation is the available fault current; for a supply transformer’s own contribution, see the transformer calculator.
Method and verification
Currents are U0 over the loop impedance, with the IEC 60909 factors applied where the mode calls for them. The UK typical Ze values and the 16 kA design figure come from the IET’s summary of ENA ER P23, confirmed by NICEIC and ELECSA; the 16 kA consumer unit rating from NICEIC. Tests reproduce the typical values (657 A for 0.35 Ω, 288 A for 0.8 Ω) and check that the three-phase estimate and the line-to-line value keep their √3/2 ratio.
A first estimate for single installations; motor contribution, peak current and the X/R ratio need a full IEC 60909 study. Updated 2026-10-14. Corrections log.